9.31.1. Scope
Add bookmark

9.31.1.1. Application
Add bookmark

(1)This Section applies to the plumbing facilities and plumbing systems within dwelling units.

(2)In occupancies other than dwelling units, plumbing facilities, grab bars, floor drains, and floor and wall finishes around urinals shall conform to Subsection 3.7.2. (See also Section 3.8. regarding barrier-free plumbing facilities.)

(3)Medical gas piping systems shall conform to Subsection 3.7.5.

9.31.2. General
Add bookmark

9.31.2.1. General
Add bookmark

(1)The construction, extension, alteration, renewal or repair of plumbing systems and sewage disposal systems shall conform to Part 7.

9.31.2.2. Corrosion Protection
Add bookmark

(1)Metal pipes in contact with cinders or other corrosive material shall be protected by a heavy coating of bitumen or other corrosion protection.

9.31.2.3. Grab Bars
Add bookmark

(1)When provided, grab bars shall be capable of resisting a load of not less than 1.3 kN applied vertically or horizontally.

9.31.3. Water Supply and Distribution
Add bookmark

9.31.3.1. Required Water Supply
Add bookmark

(1)Every dwelling unit shall be supplied with a water distribution system where a drinking water system is available.

9.31.3.2. Required Connections
Add bookmark

(1)Where a water distribution system is available, piping for hot and cold water shall be connected to every kitchen sink, lavatory, bathtub, shower, slop sink and laundry area.

(2)Piping for cold water shall be run to every water closet.

9.31.4. Required Facilities
Add bookmark

9.31.4.1. Required Fixtures
Add bookmark

(1)A kitchen sink, lavatory, bathtub or shower, and water closet shall be provided for every dwelling unit where a water distribution system is available.

9.31.4.1A. Laundry Fixtures
Add bookmark

(1)Laundry facilities or a space for laundry facilities shall be provided in every dwelling unit or grouped elsewhere in the building in a location conveniently accessible to occupants of every dwelling unit.

9.31.4.2 Hot Water Supply
Add bookmark

(1)Where a water distribution system is available a hot water supply shall be provided in every dwelling unit.

(2)A water distribution system supplying hot water to plumbing fixtures shall conform to the requirements in Subsection 7.2.10.

9.31.4.3. Floor Drains
Add bookmark

(1)Where gravity drainage to a sewer, drainage ditch or dry well is possible, a floor drain shall be installed in a basement forming part of a dwelling unit.

9.31.5. Reserved
Add bookmark

9.31.6. Service Water Heating Facilities
Add bookmark

9.31.6.1. Hot Water Supply
Add bookmark

(1)Where hot water is required to be supplied in accordance with Article 9.31.4.2., equipment shall

(a)provide an adequate supply of hot water, and

(b)be installed in conformance with Part 7.

9.31.6.1A. Hot Water Temperature
Add bookmark

(1)Where a hot water supply is required by Article 9.31.4.3., equipment shall be installed to provide to every dwelling unit an adequate supply of service hot water with a temperature range from 45°C to 60°C.

(2)An electric storage-type service water heater shall have a minimum set storage temperature of 60°C.

9.31.6.2. Equipment and Installation
Add bookmark

(1)Every service water heater and its installation shall conform to Part 7.

(2)Reserved

(3)Where the building is in a location where the spectral response acceleration, Sa(0.2), is greater than 0.55, service water heaters shall be secured to the structure to resist overturning. (See Note A-9.31.6.2.(3))

9.31.6.3. Corrosion-Resistant Coating
Add bookmark

(1)Where storage tanks for service water heaters are of steel, they shall be coated with zinc, vitreous enamel (glass lined), hydraulic cement or other corrosion-resistant material.

9.31.6.4. Fuel-Burning Heaters
Add bookmark

(1)Fuel-burning service water heaters shall be connected to a chimney flue conforming to Section 9.21.

9.31.6.5. Heating Coils
Add bookmark

(1)Heating coils of service water heaters shall not be installed in a flue or in the combustion chamber of a boiler or furnace heating a building.