Section 9.6. Glass

Section 9.6. Glass
Add bookmark

9.6.1. General
Add bookmark

9.6.1.1. Application
Add bookmark

(1)This Section applies to

(a)glass in

(i)interior doors and interior windows and their sidelights,

(ii)clothes closets,

(iii)site-built exterior windows, doors and skylights,

(iv)shower or bathtub enclosures,

(v)glazed panels and partitions, and

(b)the protection of glass.

9.6.1.2. Material Standards for Glass
Add bookmark

(1)Glass shall conform to

(a)CAN/CGSB-12.1, “Safety Glazing,”

(b)CAN/CGSB-12.2-M, “Flat, Clear Sheet Glass,”

(c)CAN/CGSB-12.3-M, “Flat, Clear Float Glass,”

(d)CAN/CGSB-12.4-M, “Heat Absorbing Glass,”

(e)CAN/CGSB-12.8, “Insulating glass units,”

(f)CAN/CGSB-12.9, “Spandrel glass,”

(g)CAN/CGSB-12.10-M, “Glass, Light and Heat Reflecting,”

(h)CAN/CGSB-12.11-M, “Wired Safety Glass,” or

(i)ASTM E2190, “Standard Specification for Insulating Glass Unit Performance and Evaluation.”

(2)Mirrored glass doors are only permitted to be used only at the entrance to clothes closets and shall conform to the requirements of CAN/CGSB-82.6-M, “Doors, Mirrored Glass, Sliding or Folding, Wardrobe.” (See Note A-9.6.1.2.(2))

(3)Mirrored glass doors reinforced with a film backing shall meet the impact resistance requirements specified in CAN/CGSB-12.5-M, “Mirrors, Silvered.”

9.6.1.3. Structural Sufficiency of Glass
Add bookmark

(1)Except as provided in Sentence (2), glass shall be designed in conformance with Article 4.3.6.1.

(2)Where the building has an essentially uniform distribution of paths for air leakage, including operable openings, but no large openings that would permit wind gusts to rapidly enter the building and the building is not in an exceptionally exposed location such as a hilltop, the maximum area of individual panes of glass for windows shall conform to

(a)Tables 9.6.1.3.-A to 9.6.1.3.-C, where the building has a height from grade to the uppermost roof of 12 m or less, and is located in a built-up area, no less than 120 m away from the boundary between this area and open terrain, or

(b)Tables 9.6.1.3.-D to 9.6.1.3.-F.

(See Note A-9.6.1.3.(2))

(3)The maximum area of individual panes of glass for doors shall conform to Table 9.6.1.3.-G.

Table 9.6.1.3.-A Maximum Glass Area for Windows in Areas for which the 1-in-50 Hourly Wind Pressure (HWP) is Less than 0.55 kPa(1)Forming Part of Clause 9.6.1.3.(2)(a)
Type of GlassMaximum Glass Area, m2
Glass Thickness, mm
2.5345681012
Annealed0.580.961.472.042.844.746.659.74
Factory-sealed insulated glass (IG) units(2)1.021.712.683.745.247.939.9213.92
Heat-strengthened or tempered1.241.932.603.183.995.556.999.74
Wired0.270.450.680.931.312.153.075.03

Notes to Table 9.6.1.3.-A:

(1)
The maximum hourly wind pressure with one chance in fifty of being exceeded in any one year, as provided in MMAH Supplementary Standard SB-1, “Climatic and Seismic Data.”
(2)
Maximum glass area values apply to IG units of two identical lites (annealed, heat-strengthened or tempered) spaced at 12.7 mm.
Table 9.6.1.3.-B Maximum Glass Area for Windows in Areas for which the 1-in-50 Hourly Wind Pressure (HWP) is Less than 0.75 kPa(1)Forming Part of Clause 9.6.1.3.(2)(a)
Type of GlassMaximum Glass Area, m2
Glass Thickness, mm
2.5345681012
Annealed0.420.681.021.422.043.344.707.65
Factory-sealed insulated glass (IG) units(2)0.721.191.852.563.646.018.3511.83
Heat-strengthened0.881.462.212.713.394.735.928.29
Tempered1.181.642.212.713.394.735.928.29
Wired0.200.320.500.680.941.552.193.60

Notes to Table 9.6.1.3.-B:

(1)
The maximum hourly wind pressure with one chance in fifty of being exceeded in any one year, as provided in MMAH Supplementary Standard SB-1, “Climatic and Seismic Data.”
(2)
Maximum glass area values apply to IG units of two identical lites (annealed, heat-strengthened or tempered) spaced at 12.7 mm.
Table 9.6.1.3.-C Maximum Glass Area for Windows in Areas for which the 1-in-50 Hourly Wind Pressure (HWP) is Less than 1.00 kPa(1)Forming Part of Clause 9.6.1.3.(2)(a)
Type of GlassMaximum Glass Area, m2
Glass Thickness, mm
2.5345681012
Annealed0.300.500.771.051.452.403.405.62
Factory-sealed insulated glass (IG) units(2)0.520.861.311.862.574.306.109.89
Heat-strengthened0.651.041.632.262.924.075.107.14
Tempered1.011.421.902.332.924.075.107.14
Wired0.160.260.380.520.711.151.632.69

Notes to Table 9.6.1.3.-C:

(1)
The maximum hourly wind pressure with one chance in fifty of being exceeded in any one year, as provided in MMAH Supplementary Standard SB-1, “Climatic and Seismic Data.”
(2)
Maximum glass area values apply to IG units of two identical lites (annealed, heat-strengthened or tempered) spaced at 12.7 mm.
Table 9.6.1.3.-D Maximum Glass Area for Windows in Areas for which the 1-in-50 Hourly Wind Pressure (HWP) is Less than 0.55 kPa – Open Terrain(1)Forming Part of Clause 9.6.1.3.(2)(b)
Type of GlassMaximum Glass Area, m2
Glass Thickness, mm
2.5345681012
Annealed0.460.751.161.602.253.765.328.70
Factory-sealed insulated glass (IG) units(2)0.801.342.112.934.106.909.6612.53
Heat-strengthened0.981.742.332.863.595.006.268.78
Tempered1.251.742.332.863.595.006.268.78
Wired0.220.360.550.761.051.752.474.09

Notes to Table 9.6.1.3.-D:

(1)
The maximum hourly wind pressure with one chance in fifty of being exceeded in any one year, as provided in MMAH Supplementary Standard SB-1, “Climatic and Seismic Data.”
(2)
Maximum glass area values apply to IG units of two identical lites (annealed, heat-strengthened or tempered) spaced at 12.7 mm.
Table 9.6.1.3.-E Maximum Glass Area for Windows in Areas for which the 1-in-50 Hourly Wind Pressure (HWP) is Less than 0.75 kPa – Open Terrain(1)Forming Part of Clause 9.6.1.3.(2)(b)
Type of GlassMaximum Glass Area, m2
Glass Thickness, mm
2.5345681012
Annealed0.330.540.831.141.612.673.756.14
Factory-sealed insulated glass (IG) units(2)0.570.941.472.042.854.756.7210.97
Heat-strengthened0.701.151.792.443.064.365.347.47
Tempered1.061.481.992.443.064.365.347.47
Wired0.160.260.400.550.761.241.772.93

Notes to Table 9.6.1.3.-E:

(1)
The maximum hourly wind pressure with one chance in fifty of being exceeded in any one year, as provided in MMAH Supplementary Standard SB-1, “Climatic and Seismic Data.”
(2)
Maximum glass area values apply to IG units of two identical lites (annealed, heat-strengthened or tempered) spaced at 12.7 mm.
Table 9.6.1.3.-F Maximum Glass Area for Windows in Areas for which the 1-in-50 Hourly Wind Pressure (HWP) is Less than 1.00 kPa – Open Terrain(1)Forming Part of Clause 9.6.1.3.(2)(b)
Type of GlassMaximum Glass Area, m2
Glass Thickness, mm
2.5345681012
Annealed0.250.400.620.841.171.942.754.50
Factory-sealed insulated glass (IG) units(2)0.420.681.041.462.053.414.877.92
Heat-strengthened0.510.841.301.792.523.694.606.44
Tempered0.921.281.722.102.633.694.606.44
Wired0.120.200.300.410.570.941.312.18

Notes to Table 9.6.1.3.-F:

(1)
The maximum hourly wind pressure with one chance in fifty of being exceeded in any one year, as provided in MMAH Supplementary Standard SB-1, “Climatic and Seismic Data.”
(2)
Maximum glass area values apply to IG units of two identical lites (annealed, heat-strengthened or tempered) spaced at 12.7 mm.
Table 9.6.1.3.-G Glass Area for DoorsForming Part of Sentence 9.6.1.3.(3)
Glass Thickness, mmMaximum Glass Area, m2(1)
Type of Glass
AnnealedAnnealed, Multiple-Glazed, Factory-Sealed UnitsLaminatedWiredHeat-StrengthenedFully TemperedFully Tempered, Multiple-Glazed, Factory-Sealed
30.500.70(2)(2)1.001.002.00
41.001.50(2)(2)1.504.004.00
51.501.50(2)(2)1.50No limitNo limit
61.501.501.201.001.50No limitNo limit

Notes to Table 9.6.1.3.-G:

(1)
See Note A-Table 9.6.1.3.-G.
(2)
Not generally available.

9.6.1.4. Types of Glass and Protection of Glass
Add bookmark

(1)Glass sidelights greater than 500 mm wide that could be mistaken for doors, glass in storm doors and glass in sliding doors within or at every entrance to a dwelling unit and in public areas shall be

(a)safety glazing of the tempered or laminated type conforming to CAN/CGSB-12.1, “Safety Glazing,” or

(b)wired glass conforming to CAN/CGSB-12.11-M, “Wired Safety Glass.”

(2)Except as provided in Sentence (4), glass in entrance doors to dwelling units and in public areas, other than the entrance doors described in Sentence (1), shall be safety glazing or wired glass of the type described in Sentence (1) where the glass area exceeds 0.5 m2 and extends to less than 900 mm from the bottom of the door.

(3)Except as provided in Sentence (4), transparent panels that could be mistaken as a means of egress shall be protected by barriers or railings.

(4)Sliding glass partitions that separate a public corridor from an adjacent occupancy and that are open during normal working hours need not conform to Sentences (2), (3) and (5), except that such partitions shall be suitably marked to indicate their existence and position.

(5)Except as provided in Sentence (4), every glass or transparent door accessible to the public shall be equipped with hardware, bars or other permanent fixtures designed so that the existence and position of such doors is readily apparent.

(6)Glazing used for a shower or bathtub enclosure shall conform to Class A of CAN/CGSB-12.1, “Safety Glazing.”